Inspection Status: Re-inspection required
Inspection History: COT - RSEL - Outdoor Lighting
| Date |
Description |
Inspector |
Results |
Comments |
| 06/17/2024 |
COT - RSEL - Outdoor Lighting |
|
Re-inspection required |
6/17/24: cut clean-outs to grade, seal around HVAC Disconnect box, properly secure HVAC Disconnect box, UV coat all exterior plastic piping, panel schedule incomplete, clean-outs missing throughout interior of home, electrical at air handler must be secured 8" from box, attic receptacles have no power, multiple circuits tied in together throughout home (not per plan). Damaged weep screed. |
| 06/24/2024 |
COT - RSEL - Outdoor Lighting |
|
Passed |
|