Inspection Status: Re-inspection required
Inspection History: RSBU - Building Final
| Date |
Description |
Inspector |
Results |
Comments |
| 12/01/2023 |
RSBU - Building Final |
|
Re-inspection required |
12/1/23: A/C condensing unit needs to be 3" above grade, anti-theft refrigeration cap's missing, j-box in attic needs to be brought down and made accessible, clearance at air handler not met minimum 30" of clearance. |
| 12/07/2023 |
RSBU - Building Final |
|
Passed |
|