Inspection Status: Re-inspection required

Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing

Date Description Inspector Results Comments
05/11/2026 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Re-inspection required 5-11-26: add shot pins 24" o.c., add anchor bolts at marked locations, replace section of sheathing at marked location along east side where sheathing gap is 1" , add nails throughout & nail flush areas marked in red, submit revision showing 2x4 studs at back restroom wall.
05/12/2026 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Passed 5-12-26: corrections made. Exterior clip/sheathing & framing approved.