Permit: TC-MDP-1124-01345

Parcel: 137041900


Addresses:

5421 S IDA LN

Inspection Status: Not Ready

Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing

Date Description Inspector Results Comments
08/27/2025 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Not Ready Nailing at exterior sheathing not per schedule. Provide cs16 straps at openings and attachments from beams to posts. SW2 not in place along with the holdowns. Add studs underneath girder trusses for bearing points. Add h25 at marked areas. (Girder trusses) Add vertical fire blocking at every 10’ at party wall. Add 3 king studs to garage opening on each end. Add shot pins to interior non bearing walls. 8/27/2025
09/10/2025 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Re-inspection required 9-10-25: missing H25 at garage south wall underneath girder truss bearing point, missing shot pins throughout-Shot pins are required within 6" at the end of each plate.
Add nails at upstairs sill plate to decking at marked locations, missing CS16 straps at beams to posts.
09/10/2025 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Re-inspection required (with fee) 9-10-25: missing H25 at garage south wall underneath girder truss bearing point, missing shot pins throughout-Shot pins are required within 6" at the end of each plate.
Add nails at upstairs sill plate to decking at marked locations, missing CS16 straps at beams to posts. Also, missing fire blocking at stairs-SEE 2018 IRC, Section R302.11 for details. A reinspection fee is being added -reschedule inspection at your convenience.
09/26/2025 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Re-inspection required 9/26/25: No access to house ( all windows and doors are boarded up), exterior sheathing must have fasteners spaced per schedule, fasteners shall not be closer than 3/8" from edge and shall not penetrate more than 1/8". Please recall inspection when boards are removed as some are covering hold downs and interior shear walls must also be inspected.
09/29/2025 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Re-inspection required 9/29/25: sheathing must be fastened per schedule, fasteners shall not penetrate more than 1/8", fasteners shall not be closer than 3/8" from edge, blocking required at edges of sheathing, anchors bolts required @32" o.c, (2) Anchor bolts required at sill plate 12" or larger, anchor bolts 12" from edge of sill plate max or 7 times the bolt diameter min. fasteners at 2nd floor sill plate to deck not complete. STOPPED INSPECTION MORE ITEMS MAY BE ADDED.
10/01/2025 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Passed