Permit: TC-MDP-1124-01342

Parcel: 137042070


Addresses:

5409 S IDA LN

Inspection Status: Re-inspection required

Inspection History: RSBU - Building Final 

Date Description Inspector Results Comments
12/18/2025 RSBU - Building Final  Re-inspection required 12/18/25: broken roof tiles 2nd floor, AFCI required at garbage disposal/dishwasher, grade must be corrected, WR receptacle required outdoors, GFCI receptacle required at laundry room, water hammer arrestor shall not be painted, mark air handler to verify correct amperage at disconnect box, verify condensate pump to be tied into air handler, secure electrical riser at main panel, insulate hot water line at water heater, post tension tag required at hose bib, roof drain must be re-routed pending on 5409, clean-outs caps at garage and grade must be opened,
12/19/2025 RSBU - Building Final  Passed