Inspection Status: Re-inspection required
Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing
| Date |
Description |
Inspector |
Results |
Comments |
| 10/22/2025 |
COT - RSBU - Exterior/Interior Clips/Sheathing/Framing |
|
Re-inspection required |
10-22-25: add anchor bolt at marked location at north firewall, add 1/2" anchor bolts to garage shear wall 32" o.c. or Ramset pins every 8" o.c., missing A35's at each of garage and at Garage shear wall every 16" o.c.,missing angle clips at upstairs firewall (every other stud), add nails to marked locations upstairs sill plate to decking, complete fire locking at stairs, add A-34's at each end gable end bracing. |
| 11/03/2025 |
COT - RSBU - Exterior/Interior Clips/Sheathing/Framing |
|
Passed |
11-3-25: exterior clips/sheathing and framing approved. Okay to continue with construction. |