Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Re-inspection required
Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing
Permit Number - TC-MDP-1124-01320
Inspection Description - COT - RSBU - Exterior/Interior Clips/Sheathing/Framing
Inspection Status - Re-inspection required
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/18/2025 | COT - RSBU - Exterior/Interior Clips/Sheathing/Framing | Re-inspection required | Gable end trusses at both ends of garage are not per the detail on page S5.2/5. Add rsp clip at the bottom of post to plate. East end of garage calls for 12” o.c walls. Shim all bearing points in garage floor trusses. Loose anchor bolts throughout. Roof shear transfer detail S5.3/17. Stopped inspection. Other items may occur. 6/18/2025 | |
| 06/26/2025 | COT - RSBU - Exterior/Interior Clips/Sheathing/Framing | Re-inspection required | 6/26/25 loose roofing at marked areas 2nd floor, detail S5.3/17, shims, and damaged truss at NW corner of house | |
| 07/22/2025 | COT - RSBU - Exterior/Interior Clips/Sheathing/Framing | Partial Pass | 7-22-25: damaged truss located at NW upstairs corner will be inspected at intermediates. Okay to dry-in roof and continue with construction at progress areas. | |
| 08/12/2025 | COT - RSBU - Exterior/Interior Clips/Sheathing/Framing | Passed | 8.12.25 Passed |