Inspection History Details
Inspection Status: Re-inspection required
Inspection History: COT - RSBU - Roof Nailing
Permit Number - TC-MDP-1124-01320
Inspection Description - COT - RSBU - Roof Nailing
Inspection Status - Re-inspection required
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/18/2025 | COT - RSBU - Roof Nailing | Re-inspection required | Gable end trusses at both ends of garage are not per the detail on page S5.2/5. Add rsp clip at the bottom of post to plate. East end of garage calls for 12” o.c walls. Shim all bearing points in garage floor trusses. Loose anchor bolts throughout. Roof shear transfer detail S5.3/17. Stopped inspection. Other items may occur. 6/18/2025 | |
| 06/26/2025 | COT - RSBU - Roof Nailing | Re-inspection required | 6/26/25 loose roofing at marked areas 2nd floor, detail S5.3/17, shims, and damaged truss at NW corner of house | |
| 07/22/2025 | COT - RSBU - Roof Nailing | Passed | 7-22-25: Okay to dry-in roof and continue with construction at progress areas. |