Permit: TC-MDP-1124-01298

Parcel: 141450570

Inspection Status: Re-inspection required

Inspection History: COT - RSBU - Interior Shear Bracing 

Date Description Inspector Results Comments
05/01/2025 COT - RSBU - Interior Shear Bracing  Re-inspection required 5/1/25: fasteners shall be no closer than 3/8" from edge, fasteners not per shearwall schedule, upstairs walk in closet must be fastened to all studs spaced at 16" o.c,
05/02/2025 COT - RSBU - Interior Shear Bracing  Re-inspection required 5-2-25, fasteners shall be no closure than 3/8" from edge. Noted: many fasteners located directly over joints/edges. This was also noted on previous inspection.
05/05/2025 COT - RSBU - Interior Shear Bracing  Re-inspection required (with fee) 5/1/25: fasteners shall be no closer than 3/8" from edge, fasteners not per shearwall schedule, upstairs walk in closet must be fastened to all studs spaced at 16" o.c,
5-2-25, fasteners shall be no closure than 3/8" from edge. Noted: many fasteners located directly over joints/edges. This was also noted on previous inspection.
5/5/25: Per previous notes. Re-inspection required with fee.
05/06/2025 COT - RSBU - Interior Shear Bracing  Passed 5/6/2025 approved. Corrections were made.