Inspection History Details
Inspection Status: Canceled
Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing
Permit Number - TC-MDP-1124-01290
Inspection Description - COT - RSBU - Exterior/Interior Clips/Sheathing/Framing
Inspection Status - Canceled
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/01/2025 | COT - RSBU - Exterior/Interior Clips/Sheathing/Framing | Canceled | Canceled per Duke. 7/1/2025 | |
| 07/02/2025 | COT - RSBU - Exterior/Interior Clips/Sheathing/Framing | Re-inspection required | Not ready. Missing h25 throughout. Missing pins at all interior bottom plates. Htt4 not nailed in place. Add a35 clips above shear wall in garage. Stopped inspection. Other items may apply. 7/2/2025 | |
| 07/07/2025 | COT - RSBU - Exterior/Interior Clips/Sheathing/Framing | Re-inspection required | 7.7.25 Shot pins required 6 inch from edge of sole plate throughout on (non load bearing). Install anchor bolts as marked, locations, Anchor bolts required within 12" of edge of exterior sole plates. A35s missing nails in multiple areas. RSP 4s required every other stud-add to marked locations, add h-25 at truss CG48C, loose roof panel on bedroom located on south-side. |
|
| 07/09/2025 | COT - RSBU - Exterior/Interior Clips/Sheathing/Framing | Re-inspection required (with fee) | 7-9-25: missing rsp4's on north side, missing anchor bolt at front entrance column, and spacing at northeast shear wall not per plans-add nails 3" o.c. And to areas where overpenetrated more than 1/16" . | |
| 07/10/2025 | COT - RSBU - Exterior/Interior Clips/Sheathing/Framing | Passed | 7-10-25: exterior clips/sheathing approved. Okay to continue with construction |