Inspection Status: Re-inspection required

Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing

Date Description Inspector Results Comments
09/18/2025 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Re-inspection required 9-18-25: add nails to all shear walls-nails can be no closer than 3/8” from joints and cannot over penetrate more than 1/16”. Add RSP4’s to stud at southside, add shot pins and anchor bolts to marked locations, add H25 to truss CG48C, missing gable bracing at back patio-see SD3/7 for details.
09/22/2025 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Re-inspection required 9/22/25
1. RSP still missing
2. Missing shot pins near bathroom sill.
09/23/2025 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Passed 9-23-25: exterior/interior clips/sheathing approved