Inspection Status: Re-inspection required

Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing

Permit Number - TC-MDP-1123-01845

Inspection Description - COT - RSBU - Exterior/Interior Clips/Sheathing/Framing

Inspection Status - Re-inspection required

Date Description Inspector Results Comments
09/23/2024 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Re-inspection required 9/23/24: Anchor bolts spacing greater than 6' o.c, more than 3 MASA clips with 1 leg up in continuous run, king studs missing throughout, MASA clips must be properly fastened, girder truss support 4x6 must be properly secured under girder per plans, h2.5 missing at trusses, shot pins at interior non bearing walls must be spaced no greater than 36" o.c, Back porch columns must be properly fastened at sill plate, HTT4 not properly installed. STOPPED INSPECTION MORE ITEMS MAY BE ADDED.
09/26/2024 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Re-inspection required 9/26/24: cs16 strap required at front bedroom top plate. Anchor bolts needed at garage. Missing h25 at trust. Shot pin needed at laundry room.
10/01/2024 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Passed