Inspection History Details
Inspection Status: Re-inspection required
Inspection History: COT - RSBU - Preslab
Permit Number - TC-MDP-1123-01843
Inspection Description - COT - RSBU - Preslab
Inspection Status - Re-inspection required
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/19/2024 | COT - RSBU - Preslab | Re-inspection required | 7/19/24: ufer not installed. Missing rebar, missing masa clips. | |
| COT - RSBU - Preslab | Passed | 7/22/24: Concrete forms are set, post tension cabling is evenly spaced, all required rebar reinforcement is installed, Ufer ground is installed in footing on garage wall, masa clips are attached to the form, underground electrical conduit is installed for kitchen island and all plumbing pipes are properly wrapped with foam wrap. Okay to pour concrete. |