Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Parcel: 136301420


Addresses:

9135 E RED BLUFF CT


Inspection Status: Re-inspection required

Inspection History: COT - RSEL - Electrical Final 

Permit Number - TC-MDP-1123-01830

Inspection Description - COT - RSEL - Electrical Final 

Inspection Status - Re-inspection required

Date Description Inspector Results Comments
12/11/2024 COT - RSEL - Electrical Final  Re-inspection required 12-11-24, provide ladder for attic access, a/c being over amped by 40 amp breaker;condenser calls for 25 max.
12/12/2024 COT - RSEL - Electrical Final  Passed 12-12-24, electrical final approved.