Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Re-inspection required
Inspection History: COT - RSME - Mechanical Final
Permit Number - TC-MDP-1123-01830
Inspection Description - COT - RSME - Mechanical Final
Inspection Status - Re-inspection required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/11/2024 | COT - RSME - Mechanical Final | Re-inspection required | 12-11-24, provide ladder for attic access, a/c being over amped by 40 amp breaker;condenser calls for 25 max. | |
12/12/2024 | COT - RSME - Mechanical Final | Passed | 12-12-24, mechanical final approved. |