Parcel: 103192970


Addresses:

2376 W OWL PERCH LP


Inspection Status: Re-inspection required

Inspection History: COT - RSEL - Electrical Final 

Permit Number - TC-MDP-1123-01805

Inspection Description - COT - RSEL - Electrical Final 

Inspection Status - Re-inspection required

Date Description Inspector Results Comments
09/05/2024 COT - RSEL - Electrical Final  Re-inspection required 9/5/24: cover plate at switch under stairs, pressure relief valve at water heater must terminate 6" above grade, spacing at receptacle outlets on kitchen counter greater than 4', kitchen circuit tied into living room receptacle, temp glass at master bath, cover plate missing at attic receptacle, cut clean outs to grade.
09/13/2024 COT - RSEL - Electrical Final  Passed