Inspection Status: Not Ready
Inspection History: RSBU - Building Final
| Date |
Description |
Inspector |
Results |
Comments |
| 07/01/2026 |
RSBU - Building Final |
|
Not Ready |
7-1-2026 Romax not permitted in flexible whip at water heater would need to be THHN. Switch at water heater is not permitted for outdoor use will need to be water resistant. Also, drywall screws are not permitted for outdoor use. Final inspection was not walked all items addressed above was caught during SWG inspection. |
| 07/20/2026 |
RSBU - Building Final |
|
Not Ready |
7/20/2026 Not ready per previous notes. Non metallic plumbing label at main panel missing. Spot 24 needs to be labeled. Provide high water loop for dishwasher. Flex in attic has to be re routed. Provide 30” in height of non obstruction to unit. |
| 07/27/2026 |
RSBU - Building Final |
|
Passed |
All corrections were made. 7/27/2026 |