Inspection Status: Re-inspection required
Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing
| Date |
Description |
Inspector |
Results |
Comments |
| 01/30/2026 |
COT - RSBU - Exterior/Interior Clips/Sheathing/Framing |
|
Re-inspection required |
|
| 01/28/2026 |
COT - RSBU - Exterior/Interior Clips/Sheathing/Framing |
|
Not Ready |
Provide another stud at north wall in garage per floor GT. Add 2’ shear panel at north wall behibehind water heater. Add shot pins to intinterior at marked areaszareas z . Add 2x at GT near stair. Add straps from headers to studs back porch. Provide cs16 straps at interior and exterior shear wall opening s. Missing screw at truss marked area East bedroom. Add screw to floor trusses. Loose shear panel at west end of bedroom. Provide bracing at gable end trusses exceeding 6’. 1/28/2026 |
| 02/03/2026 |
COT - RSBU - Exterior/Interior Clips/Sheathing/Framing |
|
Passed |
2/3/2026 approved. Correction was made. |