Inspection Status: Re-inspection required

Inspection History: COT - RSPL - Plumbing Final 

Permit Number - TC-MDP-1024-01242

Inspection Description - COT - RSPL - Plumbing Final 

Inspection Status - Re-inspection required

Date Description Inspector Results Comments
06/26/2025 COT - RSPL - Plumbing Final  Re-inspection required 6/26/25: Exterior plastic piping must be coated for UV protection, seal around stucco at T&P termination, T&P shall terminate no higher than6" above finish grade or no lower than 2x pipe diameter (finished grade not complete), properly secure dryer exhaust vent cap, aluminum conductors required Noalax, properly secure liquid tight at roof for A/C disconnect. Main panel schedule not complete/incorrect, open ground at east bedroom, anti-tip at range, pending engineering final, A/C unit is being over amped.
07/15/2025 COT - RSPL - Plumbing Final  Passed 7-15-25: plumbing final approved.