Inspection History Details
Inspection Status: Re-inspection required
Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing
Permit Number - TC-MDP-1024-01232
Inspection Description - COT - RSBU - Exterior/Interior Clips/Sheathing/Framing
Inspection Status - Re-inspection required
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/22/2025 | COT - RSBU - Exterior/Interior Clips/Sheathing/Framing | Re-inspection required | 8.22.25 Anchor bolts missing at marked locations (red) Rsp4 missing at marked location (red) Replace damaged beam or provide engineer letter/fix at garage door-to-house area as marked Replace damaged floor plate or provide engineer letter/fix at garage left as marked. Add nails to straps at back patio columns to match fastener schedule per plans Tply preventing verification of fasteners behind garage shear wall Install additional cs20 coil straps at every other stud as called out on plan areas indicated by detail SD2-1 Replace damaged diagonal bracing as marked STOPPED INSPECTION - BE ADVISED: ADDITIONAL ITEMS MAY BE ADDED |
|
| 08/29/2025 | COT - RSBU - Exterior/Interior Clips/Sheathing/Framing | Passed | 8.29.2025 Corrections made to prior 8.22.2025 inspection as well as beam and sill plate replaced. Continued on second floor and roof. |