Inspection Status: Re-inspection required

Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing

Permit Number - TC-MDP-1024-01201

Inspection Description - COT - RSBU - Exterior/Interior Clips/Sheathing/Framing

Inspection Status - Re-inspection required

Date Description Inspector Results Comments
04/08/2025 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Re-inspection required 8 April 25
1. Shot pins required throughout; 6" within edge of sill plates 48" after.
2. Damaged sill at slide door patio, on the left side facing patio.
3. Damaged sill garage entry hallway left side. Marked replace on the sill plate.
4. Nailer on truss A41AG is not per plan, calls for 2 nails @ 16" o.c.
5. Will check for A35s at shear wall on north end of garage after roof has been loaded.
6. Hold down in garage HTT4 on shear wall is pending special inspection, please do not cover nut with epoxy!.
04/11/2025 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Partial Pass 4/11/25
Partial pass; Loose nut at Shear wall HTT4. Will check at intermediate. Ok to proceed, request this inspection with intermediate.
04/24/2025 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Re-inspection required 4-24-25, nut for HTT4 at same shear wall remains loose
04/25/2025 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Passed 4-25-25, exterior clips/sheathing approved.