Inspection History Details
Inspection Status: Re-inspection required
Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/08/2025 | COT - RSBU - Exterior/Interior Clips/Sheathing/Framing | Re-inspection required | 8 April 25 1. Shot pins required throughout; 6" within edge of sill plates 48" after. 2. Damaged sill at slide door patio, on the left side facing patio. 3. Damaged sill garage entry hallway left side. Marked replace on the sill plate. 4. Nailer on truss A41AG is not per plan, calls for 2 nails @ 16" o.c. 5. Will check for A35s at shear wall on north end of garage after roof has been loaded. 6. Hold down in garage HTT4 on shear wall is pending special inspection, please do not cover nut with epoxy!. |
|
| 04/11/2025 | COT - RSBU - Exterior/Interior Clips/Sheathing/Framing | Partial Pass | 4/11/25 Partial pass; Loose nut at Shear wall HTT4. Will check at intermediate. Ok to proceed, request this inspection with intermediate. |
|
| 04/24/2025 | COT - RSBU - Exterior/Interior Clips/Sheathing/Framing | Re-inspection required | 4-24-25, nut for HTT4 at same shear wall remains loose | |
| 04/25/2025 | COT - RSBU - Exterior/Interior Clips/Sheathing/Framing | Passed | 4-25-25, exterior clips/sheathing approved. |