Inspection Status: Re-inspection required
Inspection History: RSBU - Building Final
| Date |
Description |
Inspector |
Results |
Comments |
| 04/28/2025 |
RSBU - Building Final |
|
Re-inspection required |
4/28/25: Clearance at A/C condenser unit 3" required from grade, noalax required at A/C conductors in disconnect, GFCI at garage required, cut back clean-out in bedroom and cap, A.A.V missing at kitchen island, missing clean-out at master bedroom, cut gray water clean out to grade, wiring at kitchen/dinning not per plan, thermostat must be no higher than 48" A.F.F, provide proper ladder for attic access. |
| 04/30/2025 |
RSBU - Building Final |
|
Passed |
|