Inspection Status: Re-inspection required
Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/04/2025 | COT - RSBU - Exterior/Interior Clips/Sheathing/Framing | Re-inspection required | 4 April 25 1. Damaged sill plate behind bathtub, please add anchor bolts no closer than 3.5 inches for 1/2 and 4.5 inches for 5/8 AB. 2. Shot pins needed throughout marked with an x with circle around it. Do not use cut nails. 3. Truss CG48C, per plan requires H2.5 on the bottom chord. |
|
| 04/08/2025 | COT - RSBU - Exterior/Interior Clips/Sheathing/Framing | Re-inspection required | 8 April 25 Truss CG48C per plan requires H2.5 on the bottom chord. |
|
| 04/10/2025 | COT - RSBU - Exterior/Interior Clips/Sheathing/Framing | Passed | 4/10/2025 corrections were made. |