Parcel: 136480490


Addresses:

9702 E GRAY HAWK DR


Inspection Status: Re-inspection required

Inspection History: RSBU - Building Final 

Permit Number - TC-MDP-1023-01670

Inspection Description - RSBU - Building Final 

Inspection Status - Re-inspection required

Date Description Inspector Results Comments
07/03/2024 RSBU - Building Final  Re-inspection required Mechanical equipment is installed and operational. Dead front on electrical panel needs to be properly installed so breakers are aligned with edge of opening. All romex wire sleeves used for labeling circuits must be removed from inside of electrical panel. Clean-outs need to be cut down to grade.
07/09/2024 RSBU - Building Final  Passed