Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
Inspection Status: Re-inspection required
Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing
| Date |
Description |
Inspector |
Results |
Comments |
| 03/06/2024 |
COT - RSBU - Exterior/Interior Clips/Sheathing/Framing |
|
Re-inspection required |
3/6/24: M.A.S.A. Clips spacing greater than 6' at multiple locations (add anchor bolts), spalling at STHD 14 at garage greater than 4" will need RFI on replacement, Shear wall fastening schedule at back porch not per schedule. H2.5 clip missing throughout. HTT4 not in place at time of inspection at garage shear wall. |
| 03/14/2024 |
COT - RSBU - Exterior/Interior Clips/Sheathing/Framing |
|
Partial Pass |
HTT missing nails, over spalled hold-down at front of garage. Partial-pass. |
| 05/08/2024 |
COT - RSBU - Exterior/Interior Clips/Sheathing/Framing |
|
Passed |
|