Inspection Status: Re-inspection required

Inspection History: RSBU - Building Final 

Permit Number - TC-MDP-1023-01624

Inspection Description - RSBU - Building Final 

Inspection Status - Re-inspection required

Date Description Inspector Results Comments
06/21/2024 RSBU - Building Final  Re-inspection required 6/21/24: T&P discharge must terminate 6” above grade, HVAC unit must be 3” above grade,HVAC unit being over amped (max 25), water heater needs to be on its own circuit
06/27/2024 RSBU - Building Final  Passed Corrections were made. 6/27/2024