Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
Inspection Status: Re-inspection required
Inspection History: COT - RSBU - Roof NailingĀ
| Date |
Description |
Inspector |
Results |
Comments |
| 03/21/2024 |
COT - RSBU - Roof NailingĀ |
|
Re-inspection required |
3/21/24: Shearwall 11 nail schedule not per plan, shearwall 11 at master missing anchor bolt with 3"x3" plate (spacing is greater than 23" o.c), shearwall 11 at entrance missing anchor bolt (spacing greater than 23" o.c), multiple anchor bolts missing 12" from edge/split of bottom plate, H2.5 clip missing at garage, roof nailing not per schedule throughout. |
| 03/25/2024 |
COT - RSBU - Roof NailingĀ |
|
Passed |
|