Permit: TC-MDP-0926-00757

Parcel: 11615190J


Addresses:

524 N COVILLE DR

Inspection Status: Not Ready

Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing

Date Description Inspector Results Comments
10/16/2026 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Not Ready Provide additional 2x6 stud at north wall for girder truss at garage. Provide 8” o.c throughout all window opening from trimmer to king studs. All shear wall nailing over penetrated. Shw 11 at south east corner missing nails per schedule. Missing dtc clip or deflector screw at non bearing wall near entry. Provide 2 cripple studs at girder truss at entry. At all double top plate splices provide 12 16d nails on each side. 10/15/2026
10/19/2026 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Passed 10/19/2026 approved. All corrections were made.