Inspection Status: Re-inspection required
Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing
Permit Number - TC-MDP-0925-00585
Inspection Description - COT - RSBU - Exterior/Interior Clips/Sheathing/Framing
Inspection Status - Re-inspection required
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/06/2026 | COT - RSBU - Exterior/Interior Clips/Sheathing/Framing | Re-inspection required | 03/06/2026 Add (2)studs and 6" structural screw to end of floor girder truss as marked in garage, add anchor bolts at marked locations on shearwall in garage and along outside sill plate as marked, add 6" structural screws to trusses as marked - some screws are only going through one top plate. Missing bracing on trusses A2, A4, A5 per truss calcs. Engineer fix/letter on damaged web required on truss A6 near stairs as marked. |