Parcel: 141461170


Addresses:

9551 E FRIEDEL DR


Inspection Status: Re-inspection required

Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing

Permit Number - TC-MDP-0925-00585

Inspection Description - COT - RSBU - Exterior/Interior Clips/Sheathing/Framing

Inspection Status - Re-inspection required

Date Description Inspector Results Comments
03/06/2026 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Re-inspection required 03/06/2026
Add (2)studs and 6" structural screw to end of floor girder truss as marked in garage, add anchor bolts at marked locations on shearwall in garage and along outside sill plate as marked, add 6" structural screws to trusses as marked - some screws are only going through one top plate. Missing bracing on trusses A2, A4, A5 per truss calcs. Engineer fix/letter on damaged web required on truss A6 near stairs as marked.