Inspection History Details
Inspection Status: Canceled
Inspection History: RSBU - Building Final
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/30/2026 | RSBU - Building Final | Canceled | ||
| 07/01/2026 | RSBU - Building Final | Re-inspection required | 7-1-26: lower thermostat downstairs to 48" o.c., a/c condenser is over amped-max should be a 40 amp breaker, missing globe at attic light fixture, missing non-metallic label at main panel. | |
| 07/08/2026 | RSBU - Building Final | Passed | 07/08/2026 Corrections made to prior inspection. |