Inspection History: COT - RSBU - Roof Nailing
Permit Number - TC-MDP-0925-00559
Inspection Description - COT - RSBU - Roof Nailing
Inspection Status - Requested
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| COT - RSBU - Roof Nailing | Requested | |||
| 01/22/2026 | COT - RSBU - Roof Nailing | Not Ready | Not ready provide clean work areas . Trade working inside prior to fame approval. 1/22/2026 | |
| 01/27/2026 | COT - RSBU - Roof Nailing | Re-inspection required | 1/27/26: Anchor bolts must be spaced at 24"O.C at shear wall 5 at first floor throughout, Anchor bolts required 12" from edge of sill plate, anchor bolts required to be spaced no more then 48" o.c at non-shear walls, anchor bolts at shear wall in garage must be exposed to verify spacing, per detail SD3/3 H2.5 required at floor truss by pwd room 1st floor, per SD3/1 CS16 strap required at 48" o.c at exterior rim blocking, cs16 at garage opening must be 54", shear wall fasteners shall be 3/8" from edge and shall not penetrate more than 1/8", shear wall fasteners must be installed per schedule, anchor bolts required 12" from hold down, 2nd floor holdowns missing throughout and shall be appropriate length with correct number of fasteners, STOPPED INSPECTION MORE ITEMS MAY BE ADDED. |