Inspection Status: Re-inspection required

Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing

Permit Number - TC-MDP-0925-00518

Inspection Description - COT - RSBU - Exterior/Interior Clips/Sheathing/Framing

Inspection Status - Re-inspection required

Date Description Inspector Results Comments
09/30/2025 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Re-inspection required 9.30.25
Only 1 in 3 masa can have a leg up
AB may be no closer than 7x bolt diameter to edge/splice of plate
Over penetrations at shear walls
Shot-pin spacing at interior walls not per plans
Minimum 2 shotpins per interior plate
AB at shear11 must be no greater than 23OC
STOPPED INSPECTION: more items may be added
10/01/2025 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Re-inspection required (with fee) 10.1.25
Multiple issues persist.
Truss calcs on site do not match
Reinspection requires fee
10/03/2025 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Passed