Inspection History Details
Inspection Status: Re-inspection required
Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing
Permit Number - TC-MDP-0925-00518
Inspection Description - COT - RSBU - Exterior/Interior Clips/Sheathing/Framing
Inspection Status - Re-inspection required
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/30/2025 | COT - RSBU - Exterior/Interior Clips/Sheathing/Framing | Re-inspection required | 9.30.25 Only 1 in 3 masa can have a leg up AB may be no closer than 7x bolt diameter to edge/splice of plate Over penetrations at shear walls Shot-pin spacing at interior walls not per plans Minimum 2 shotpins per interior plate AB at shear11 must be no greater than 23OC STOPPED INSPECTION: more items may be added |
|
| 10/01/2025 | COT - RSBU - Exterior/Interior Clips/Sheathing/Framing | Re-inspection required (with fee) | 10.1.25 Multiple issues persist. Truss calcs on site do not match Reinspection requires fee |
|
| 10/03/2025 | COT - RSBU - Exterior/Interior Clips/Sheathing/Framing | Passed |