Inspection History Details
Inspection Status: Re-inspection required
Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/09/2026 | COT - RSBU - Exterior/Interior Clips/Sheathing/Framing | Re-inspection required | 6/9/26: Strapping at garage opening not per detail 307.A, fasteners at garage opening not per detail 307.A, Shearwall fasteners not per plan (no closer than 3/8" from edge and shall not penetrate more than 1/8"), anchor bolt spacing at SW11 not per plans (max 23" o.c), (3)king stud required at window opening in den, anchor bolts shall be placed no closer than 7x bolt diameter from edge, trimmer studs shall bare full contact at back patio S.G.D, fasteners at SW9 not per schedule, studs in bedroom 3 not bearing full length at bottom plate, double studs under G.T must be properly secured to each other, SW9 at garage must be properly nailed off, shot pins at interior non load bearing walls 32" o.c, truss bracing at mechanical area at incorrect web. ROOF NAILING WAS NOT WALKED. | |
| 06/11/2026 | COT - RSBU - Exterior/Interior Clips/Sheathing/Framing | Re-inspection required (with fee) | 6.11.26 Some corrections remain yet to be made. Check all notes and areas marked on site in red. |
|
| 06/22/2026 | COT - RSBU - Exterior/Interior Clips/Sheathing/Framing | Passed | 6.22.26 Approved |