Permit: TC-MDP-0925-00501

Parcel: 141156970

Inspection Status: Re-inspection required

Inspection History: COT - RSME - Mechanical Final 

Date Description Inspector Results Comments
09/23/2026 COT - RSME - Mechanical Final  Re-inspection required 9/23/26: gas meter not installed, missing conditions, missing dishwasher, stove/anti tip device, missing lavatory plumbing fixtures, missing receptacle covers throughout. HOUSE IS NOT READY-STOPPED INSPECTION-ADDITIONAL ITEMS MAY BE NOTED.
COT - RSME - Mechanical Final  Re-inspection required 9/28/26: check off non-metallic plumbing at main panel, missing p-traps and lavatory fixtures at restrooms, add a support to laundry exhaust in attic and supports to flex at 4' intervals, provide a 3" clearance at hvac pad.
COT - RSME - Mechanical Final  Scheduled