Inspection History Details
Inspection Status: Re-inspection required
Inspection History: COT - RSME - Mechanical Final
Permit Number - TC-MDP-0924-01122
Inspection Description - COT - RSME - Mechanical Final
Inspection Status - Re-inspection required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/11/2025 | COT - RSME - Mechanical Final | Re-inspection required | 11 March 25 1. Wrong size breaker for HVAC condenser. Needs max 30 amps. 2. Dead front on electrical panel needs to be secured properly, gaping holes in the middle and top. 3. Dryer vent backdraft damper west side roof appears to be falling off or is wrong size. 4. Do not cover fire label in garage entry door. 5. HVAC line set needs to secured, and is also embedded into hvac air supply flex. |
|
COT - RSME - Mechanical Final | Scheduled |