Inspection History Details
Inspection Status: Partial Pass
Inspection History: COT - RSEL - Grounding/BondingĀ
Permit Number - TC-MDP-0924-01121
Inspection Description - COT - RSEL - Grounding/BondingĀ
Inspection Status - Partial Pass
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/18/2024 | COT - RSEL - Grounding/BondingĀ | Partial Pass | Concrete forms are set, masa clips are spaced 32" apart, hold down straps are placed per the plan, underground electrical conduit is installed for kitchen island, Ufer ground is in place, and all underground plumbing pipes are properly wrapped with foam. Okay to pour concrete. |