Permit: TC-MDP-0924-01056

Parcel: 141450560

Inspection Status: Re-inspection required

Inspection History: COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in.

Date Description Inspector Results Comments
06/06/2025 COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. Re-inspection required 6-6-25: add receptacle at north wall of kitchen- we are wired per plans, however, a receptacle is required within 6' of a door and spaced no more than 12' thereafter. Add Boca plate to protect Line set and seal vapor penetration at marked locations -northwest bedroom, shower not under test.
06/09/2025 COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. Re-inspection required 6-9-25: seal vapor barrier at marked location at northwest bedroom and reattach Boca plate at kitchen sill plate.
06/10/2025 COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, HVAC and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. Passed 6-10-25: Boca plate at kitchen not attached with nails. Nail plate installed. EWS