Inspection Status: Re-inspection required

Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing

Permit Number - TC-MDP-0924-01019

Inspection Description - COT - RSBU - Exterior/Interior Clips/Sheathing/Framing

Inspection Status - Re-inspection required

Date Description Inspector Results Comments
11/19/2024 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Re-inspection required 11-19-24, add anchor bolts to marked areas, A-35'S not fully fastened to top plates on east and west walls (in many places framers are using 1 nail). H-25'S must be nailed to interior load bearing framing at intermediate inspection.
11/22/2024 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Re-inspection required 11-22-24, anchor bolts are required within 12" of beginning of an edge. On the southeast corner of exterior wall near back patio there are 3 masa clips in a row with 1 leg up and a shot pin in between. An anchor bolt is required as a shot pin does not suffice. Also, I observed a few A-35's on the Southwest bedroom where the nails were added but not fastened all the way down to top plates. Have framers walk it in its entirety and properly nail down clips to areas in question.
12/13/2024 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Passed 12/13/24 corrections have been made. Ok to proceed.