Inspection Status: Partial Pass

Inspection History: COT - RSEL - Grounding/Bonding 

Permit Number - TC-MDP-0924-01012

Inspection Description - COT - RSEL - Grounding/Bonding 

Inspection Status - Partial Pass

Date Description Inspector Results Comments
08/25/2025 COT - RSEL - Grounding/Bonding  Partial Pass
10/02/2025 COT - RSEL - Grounding/Bonding  Re-inspection required 10/2/25: all plumbing pipes outside thermal envelope must be insulated with minimum R-3, missing receptacle at laundry room, seal all penetrations through top plate, missing smoke detector at kitchen, DWV must be under test, Garage light fixture is exceeding box fill, thermostat shall be no higher than 48" o.c AFF, properly secure exhaust fan flex, garage receptacles must be 12-2 for 20 amp circuit (3) required, proper slope required at HVAC primary and secondary condensate drain, penetration through vapor barrier must be sealed at north east bathroom, mudring required at UFER CONNECTION, transfer air required at north east bedroom 14" flex, seal all area of torn flex sheathing, attic access requirements not met 30" head room clearance, support fresh air intake flex,
10/06/2025 COT - RSEL - Grounding/Bonding  Passed