Inspection Status: Re-inspection required

Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing

Permit Number - TC-MDP-0924-01009

Inspection Description - COT - RSBU - Exterior/Interior Clips/Sheathing/Framing

Inspection Status - Re-inspection required

Date Description Inspector Results Comments
COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Re-inspection required 18 March 25
1. Broken Truss web T19, Web 7. Provide engineer letter with repair.
2. Shear wall anchors need to 32" on center.
3. Provide Truss plan for T19, it is missing in the truss Calcs binder.
03/18/2025 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Re-inspection required 18 March 25
1. Broken Truss web T19, Web 7. Provide engineer letter with repair.
2. Shear wall anchors need to 32" on center.
3. Provide Truss plan for T19, it is missing in the truss Calcs binder.
4. Interior Load bearing wall needs to have anchor bolts every 6ft.
03/19/2025 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Partial Pass Partial pass pending engineering fix on truss t19, check at intermediate stage
04/03/2025 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Passed 3 April 25
pass