Inspection Status: Not Ready

Inspection History: COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in.

Permit Number - TC-MDP-0923-01588

Inspection Description - COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in.

Inspection Status - Not Ready

Date Description Inspector Results Comments
06/18/2024 COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. Not Ready Not ready. Leak at laundry room area. Add nail plates to anything that is less than an 1 1/4". Fire foam all top penetrations. Add blocking at all registers. Missing receptacles at kitchen island. STOPPED INSPECTION. 6/18/2024
06/21/2024 COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. Re-inspection required Not ready. Leak at laundry room area. Add nail plates to anything that is less than an 1 1/4". Fire foam all top penetrations. Add blocking at all registers. Missing receptacles at kitchen island. STOPPED INSPECTION. 6/18/2024
6/21/24: per previous notes, plenum at first floor needs to be properly sealed, DWV needs support throughout at above ceiling, support on exhaust fan flex, seal penetrations through vapor barrier, refrigerant lines missing, nail strap at refrigerant lines (over notched top plate)
06/26/2024 COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. Re-inspection required Abs line has been punctured with staples. Insulate water line in garage area. Plenum at first floor needs to be properly sealed. 6/26/2024
06/28/2024 COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. Re-inspection required Provide DWV TEST to verify the abs line has been taking care of. 6/28/2024
07/02/2024 COT - RSBU - Residential Intermediate may include Framing, Electrical, Plumbing, and/or Mechanical work. Only one inspection may be attached for all trades for final rough-in. Passed Corrections were made. 7/2/2024