Permit: TC-MDP-0923-01538

Parcel: 120084220


Addresses:

104 W OKLAHOMA ST

Inspection Status: Re-inspection required

Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing

Date Description Inspector Results Comments
10/30/2023 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Re-inspection required 10/30/23: firewall 5/8" type x needs to be nailed per schedule, bottom plate at firewall on both sides require shot pins at 24" o.c, 2x6" studs at south unit at water heater spaced greater than 16" o.c, properly fasten all anchor bolts throughout.
10/31/2023 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Passed 10/30/23: firewall 5/8" type x needs to be nailed per schedule, bottom plate at firewall on both sides require shot pins at 24" o.c, 2x6" studs at south unit at water heater spaced greater than 16" o.c, properly fasten all anchor bolts throughout.
10/31/23: corrections made