Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: TC-MDP-0923-01536

Parcel: 118220060

Inspection Status: Re-inspection required

Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing

Date Description Inspector Results Comments
12/11/2023 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Re-inspection required 12/11/23: north wall of 2 bedroom unit has anchor bolt spaced greater than 48", anchor bolts must be no more than 12" from edge of bottom plate and no less than 4", south wall of 3 bedroom unit has anchor bolt spacing greater than 48", h2.5 clip missing at truss at 3 unit apartment, interior walls shot pins not per schedule. check at intermediate
12/14/2023 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Passed