Inspection Status: Re-inspection required
Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing
| Date |
Description |
Inspector |
Results |
Comments |
| 12/11/2023 |
COT - RSBU - Exterior/Interior Clips/Sheathing/Framing |
|
Re-inspection required |
12/11/23: north wall of 2 bedroom unit has anchor bolt spaced greater than 48", anchor bolts must be no more than 12" from edge of bottom plate and no less than 4", south wall of 3 bedroom unit has anchor bolt spacing greater than 48", h2.5 clip missing at truss at 3 unit apartment, interior walls shot pins not per schedule. check at intermediate |
| 12/14/2023 |
COT - RSBU - Exterior/Interior Clips/Sheathing/Framing |
|
Passed |
|