Inspection History Details
Inspection Status: Partial Pass
Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing
Permit Number - TC-MDP-0825-00488
Inspection Description - COT - RSBU - Exterior/Interior Clips/Sheathing/Framing
Inspection Status - Partial Pass
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/06/2026 | COT - RSBU - Exterior/Interior Clips/Sheathing/Framing | Partial Pass | 01/06/2026 Partial pass. Corrections made to prior 12/31/25 inspection except engineer fix/letter for rear column not poured correctly. Verify at intermediates. |
|
| 01/21/2026 | COT - RSBU - Exterior/Interior Clips/Sheathing/Framing | Passed | 01/21/2026 Verified fix to rear porch column. |
|
| 12/31/2025 | COT - RSBU - Exterior/Interior Clips/Sheathing/Framing | Re-inspection required | 12/31/2025 Engineer fix/letter required at rear patio column not poured correctly. Add anchor bolts at marked locations, add shot pins as marked 6" from sill plate edges on interior walls, add roof nails to panel at marked location on floor in great room, add washer plates to anchor bolts at SW11 in bedroom 3. Add anchor bolts on sill plate edges within 12" at SW9 inside garage - no washer plates required. Add 2x4 post on interior bearing wall to make 3-point bearing point for girder truss A8G. A2M trusses need bracing. |