Inspection Status: Re-inspection required

Inspection History: COT - RSBU - Excavation/Rebar/Zoning 

Date Description Inspector Results Comments
07/06/2026 COT - RSBU - Excavation/Rebar/Zoning  Re-inspection required 7/6/26: Properly compact pad, setbacks off 4 1/2" at west side of home (please revise site-plan), properly slope pt and pad at garage, footings shall be 12" x12" (WXH), pt cable shall not have more than 12" exposed cable at stationary end and no more than 1" at pull end, end cap missing at stationary end throughout.
07/07/2026 COT - RSBU - Excavation/Rebar/Zoning  Re-inspection required 7.7.26: properly compact pad, set back off 4 1/2" at west side of home (revision required), properly slope pt cables at garage, duct tape not allowed on pt cable, end caps still missing on stationary ends.
07/08/2026 COT - RSBU - Excavation/Rebar/Zoning  Re-inspection required (with fee) 7-8-2026 properly compact pad, set back off 4 1/2" at west side of home (revision required), properly slope pt cables at garage, end caps still missing on stationary ends.
07/09/2026 COT - RSBU - Excavation/Rebar/Zoning  Passed