Inspection History Details
Inspection Status: Re-inspection required
Inspection History: COT - RSEL - Electrical Final
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/27/2026 | COT - RSEL - Electrical Final | Re-inspection required | Smoke detectors to close to the wall. East bedroom along with primary room. T stat shall be at 48”. Re secure seal tight at disconnect 12” from Box. Provide refrigerant caps at condenser unit. Coat exterior pipes. Provide ko seal at main panel. Label non metallic at main panel. Specify location of circuit 14 at main panel. All outstanding conditions shall be met prior to building final. 7/27/2026 |
|
| 07/28/2026 | COT - RSEL - Electrical Final | Passed | 07/28/2026 Corrections made. Partial pass pending open conditions paperwork. |