Permit: TC-MDP-0825-00476

Parcel: 14101013E


Addresses:

9771 E PANOPEIA DR

Inspection Status: Re-inspection required

Inspection History: COT - RSME - Mechanical Final 

Date Description Inspector Results Comments
07/27/2026 COT - RSME - Mechanical Final  Re-inspection required Smoke detectors to close to the wall. East bedroom along with primary room. T stat shall be at 48”. Re secure seal tight at disconnect 12” from
Box. Provide refrigerant caps at condenser unit. Coat exterior pipes. Provide ko seal at main panel. Label non metallic at main panel. Specify location of circuit 14 at main panel. All outstanding conditions shall be met prior to building final. 7/27/2026
07/28/2026 COT - RSME - Mechanical Final  Passed 07/28/2026
Corrections made. Partial pass pending open conditions paperwork.