Inspection History Details
Inspection Status: Re-inspection required
Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/30/2025 | COT - RSBU - Exterior/Interior Clips/Sheathing/Framing | Re-inspection required | 9.30.25 RSP4 MISSING NORTH SIDE AT TOP Anchor bolts can be no closer than 7x diameter at edge of sill plate (north east side where masa covers both sides of splice) Nails at sheer sheathing over penetrate throughout Shot pin spacing not per plan in multiple areas |
|
| 10/01/2025 | COT - RSBU - Exterior/Interior Clips/Sheathing/Framing | Canceled | 10.1.25 Work being conducted on site, trip hazards and other hazards prevalent along with visual obstruction. Site not suitable for inspection. Reinspection requires fee. |
|
| 10/03/2025 | COT - RSBU - Exterior/Interior Clips/Sheathing/Framing | Passed |