Inspection Status: Re-inspection required

Inspection History: COT - RSBU - Exterior/Interior Clips/Sheathing/Framing

Permit Number - TC-MDP-0825-00470

Inspection Description - COT - RSBU - Exterior/Interior Clips/Sheathing/Framing

Inspection Status - Re-inspection required

Date Description Inspector Results Comments
09/30/2025 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Re-inspection required 9.30.25
RSP4 MISSING NORTH SIDE AT TOP
Anchor bolts can be no closer than 7x diameter at edge of sill plate (north east side where masa covers both sides of splice)
Nails at sheer sheathing over penetrate throughout
Shot pin spacing not per plan in multiple areas
10/01/2025 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Canceled 10.1.25
Work being conducted on site, trip hazards and other hazards prevalent along with visual obstruction. Site not suitable for inspection. Reinspection requires fee.
10/03/2025 COT - RSBU - Exterior/Interior Clips/Sheathing/Framing Passed