Inspection Status: Re-inspection required

Inspection History: COT - RSME - Mechanical Final 

Permit Number - TC-MDP-0825-00470

Inspection Description - COT - RSME - Mechanical Final 

Inspection Status - Re-inspection required

Date Description Inspector Results Comments
01/20/2026 COT - RSME - Mechanical Final  Re-inspection required 1/20/26: hvac condenser Disconnect box requires 3' clearance in front, accessible route does not meet requirements, properly secure conduit at wall will appropriate fasteners,
KO at main panel must be sealed, thermostat shall be no higher than 48" above finish floor, no attic access, no garage access, domestic water has not been hooked up, sewer connection has not been made, expansion tank required at water heater due to a closed loop system. Stopped inspection more items may be added. Please call future inspections under commercial permit for sales office and model home (this permit is directly correlated with the SFR)
11/17/2025 COT - RSME - Mechanical Final  Not Ready Use as a sales office will be tied to separate permit.