Inspection History Details
Inspection Status: Re-inspection required
Inspection History: COT - RSME - Mechanical Final
Permit Number - TC-MDP-0825-00470
Inspection Description - COT - RSME - Mechanical Final
Inspection Status - Re-inspection required
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/20/2026 | COT - RSME - Mechanical Final | Re-inspection required | 1/20/26: hvac condenser Disconnect box requires 3' clearance in front, accessible route does not meet requirements, properly secure conduit at wall will appropriate fasteners, KO at main panel must be sealed, thermostat shall be no higher than 48" above finish floor, no attic access, no garage access, domestic water has not been hooked up, sewer connection has not been made, expansion tank required at water heater due to a closed loop system. Stopped inspection more items may be added. Please call future inspections under commercial permit for sales office and model home (this permit is directly correlated with the SFR) |
|
| 11/17/2025 | COT - RSME - Mechanical Final | Not Ready | Use as a sales office will be tied to separate permit. |