Inspection History Details
Inspection Status: Re-inspection required
Inspection History: COT - RSEL - Electrical Final
Permit Number - TC-MDP-0824-00926
Inspection Description - COT - RSEL - Electrical Final
Inspection Status - Re-inspection required
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/04/2025 | COT - RSEL - Electrical Final | Re-inspection required | 6/4/25 1. Laundry circuit is tied into bathroom. 2. HVAC Max Fuse is 25A, you have 50A breaker/Fuse. 3. All exterior plastic piping must be painted to prevent U.V. Damage. |
|
| 06/09/2025 | COT - RSEL - Electrical Final | Passed | passed final 6/9/25 |